Welcome to Shanghai HI RUN system control Co., Ltd!

Contact us Collection site Online Message

National Service Hotline 021-63526338
  • Home
  • About Us
  • {dede:field name='typeurl'/}'——{dede:field name='typename'/} {dede:channel type='son' noself='yes' } /en/about/ —— About Us {/dede:channel}
  • Product Center
  • {dede:field name='typeurl'/}'——{dede:field name='typename'/} {dede:channel type='son' noself='yes' } /en/Product Center/ —— Product Center {/dede:channel}
  • News Information
  • {dede:field name='typeurl'/}'——{dede:field name='typename'/} {dede:channel type='son' noself='yes' } /en/News Information/ —— News Information {/dede:channel}
  • Engineering Case
  • {dede:field name='typeurl'/}'——{dede:field name='typename'/} {dede:channel type='son' noself='yes' } /en/Engineering Case/ —— Engineering Case {/dede:channel}
  • Sales Outlets
  • {dede:field name='typeurl'/}'——{dede:field name='typename'/} {dede:channel type='son' noself='yes' } /en/Sales Outlets/ —— Sales Outlets {/dede:channel}
  • Download
  • {dede:field name='typeurl'/}'——{dede:field name='typename'/} {dede:channel type='son' noself='yes' } /Download/ —— Download {/dede:channel}
  • Contact Us
  • {dede:field name='typeurl'/}'——{dede:field name='typename'/} {dede:channel type='son' noself='yes' } /en/Contact Us/ —— Contact Us {/dede:channel}
  • Online Message

Hot keyword search:

AS/NZS 1972:2006 Cables Location:Home> > English > Product Center > Mining Cables > AS/NZS 1972:2006 Cables >

XLPE Insulated 6.35/11KV & 12.7/22KV

Article source:http://www.trcables.com/   author:上海嗨润   Release time:2018-02-02 14:46   Browse times:second

 XLPE Insulated 6.35/11KV & 12.7/22KV

Applications

Thesecables are used as HV feeder cables in fixed conditions.

Standards

XLPE Insulated 6.35/11KV & 12.7/22KV

AS/NZS 1972:2006

AS/NZS 1125

AS/NZS 3808

Construction

Conductors: Stranded plain copper conductor.

Insulation: XLPE.

Individual Screen (earth conductor): Copper wire.

Inner Sheath: PVC sheath.

Armour: Galvanized steel wire armour.

Outer Sheath: PVC sheathto AS/NZS 1429.1.

Dimensions and Weight

Nominal Conductor Area Nominal Conductor Diameter Insulation Thickness Core screen Armour Wire Diameter Nominal Sheath Thickness Nominal Overall Diameter Nominal Weight
Strand Size Area
of Screen
mm² mm mm mm mm² mm mm mm kg/100m
6.35/11kV
16 4.8 3.4 10/0.85 5.7 2.00 2.4 46.6 330
25 5.8 3.4 10/0.85 5.7 2.50 2.5 50.1 415
35 6.8 3.4 11/0.85 6.2 2.50 2.6 52.8 475
50 8.0 3.4 15/0.85 8.5 2.50 2.7 55.7 540
70 9.6 3.4 21/0.85 11.9 2.50 2.8 59.6 645
95 11.5 3.4 29/0.85 16.5 2.50 2.9 63.9 775
120 13.1 3.4 36/0.85 20.4 2.50 3.1 67.9 905
150 14.5 3.4 44/0.85 25.0 2.50 3.2 71.5 1030
185 16.1 3.4 22/1.35 31.5 3.15 3.3 78.6 1280
240 18.5 3.4 29/1.35 41.5 3.15 3.5 84.7 1550
300 20.7 3.4 37/1.35 53.0 3.15 3.7 90.4 1820
400 23.6 3.4 47/1.35 67.3 3.15 4.0 97.9 2230
12.7/22kV
35 6.8 5.5 14/0.85 7.9 2.5 2.9 63.2 600
50 8.0 5.5 15/0.85 8.5 2.5 3.0 66.0 665
70 9.6 5.5 21/0.85 11.9 2.5 3.1 69.9 775
95 11.5 5.5 29/0.85 16.5 2.5 3.3 74.4 920
120 13.1 5.5 36/0.85 20.4 3.15 3.4 79.5 1140
150 14.5 5.5 44/0.85 25.0 3.15 3.5 83.1 1280
185 16.1 5.5 22/1.35 31.5 3.15 3.7 89.1 1450
240 18.5 5.5 29/1.35 41.5 3.15 3.9 95.0 1720
300 20.7 5.5 37/1.35 53.0 3.15 4.1 101.1 2010
400 23.6 5.5 47/1.35 67.3 3.15 4.3 108.2 2420